Solution Overview
The IQS160 On-site Transformer Thermometer Calibration Solutionis designed primarily for calibrating pressure thermometers, top-oil temperature indicators, winding temperature indicators and platinum resistance thermometers used in power grid systems. It features fast temperature ramping and variable-speed heating/cooling functions.
This solution complies with the following specifications:
JB/T 6302-2016Top-oil Temperature Indicators for Transformers
JB/T 8450-2016Winding Temperature Indicators for Transformers
JJG 310-2002Verification Regulation of Pressure Thermometers
The device supports simultaneous input of 4 channels of temperature switch testing and calculation results, with forward and reverse stroke testing. In accordance with calibration specification requirements, it records and calculates: calibration temperature, operating temperature, operating temperature change; return temperature, return temperature change; operating error and switching error.
It features a large touchscreen display showing heating and constant-temperature process curves, temperature change per minute, 10-minute temperature fluctuation, and constant-temperature duration. With a wide temperature range, fast heating/cooling, and variable-speed heating/cooling, it also includes linear correction for control deviation.
Technical Parameters
Temperature range:(0 ~ 160) °C
Stability:±0.005 °C
Accuracy:±0.03 °C
Fluctuation:±0.005 °C / 10 min
Horizontal uniformity:0.005 °C
Resolution:0.01 °C
Zone:0.01 °C
Heating time:25 min (room temperature to 100 °C)
Cooling time:30 min (100 °C to 20 °C)
Working medium:Silicone oil
Power:300 W
Weight:12 kg